Lenze EVS9332xS Manual de usuario Pagina 161

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 264
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 160
Function library
Function blocks
3.2.39 Internal motor control (MCTRL)
3−109
l
EDSVS9332S−EXT EN 2.0
3.2.39.8 Quick stop QSP
The QSP function is used to stop the drive within an adjustable time independently of the setpoint
selection.
The QSP function is active
l if the input MCTRL−QSP is triggered with HIGH.
l if the controller is triggered via the control words (DCTRL).
Function:
l If torque control has been selected, it will be deactivated. The drive is controlled by the speed
controller.
l The speed runs with the deceleration time set under C0105 to zero speed.
l The torque limitations MCTRL−LO−M−LIM and MCTRL−HI−M−LIM are deactivated.
l The angle controller is activated. If the rotor position is shifted actively, the drive generates a
torque against this displacement if:
C0254 is not zero
The input MCTRL−PHI−LIM is triggered with a value > 0 %.
( Stop!
If the field is weakened manually (MCTRL−FLD−WEAK < 100%), the drive is unable
to generate the max. torque.
Vista de pagina 160
1 2 ... 156 157 158 159 160 161 162 163 164 165 166 ... 263 264

Comentarios a estos manuales

Sin comentarios