EDS94AYFLF EN 3.2 - 10/2010 L 35
Digital frequency extension module | Parameter setting & configuration
Parameter reference
Parameter list | C13036
C13036
C13037
C13040
C13041
Parameter | Name:
C13036 | Actual position DFIN
Data type: INTEGER_32
Index: 11539
d
= 2D13
h
Display range (min. value | unit | max. value)
-214748.3647 Unit 214748.3647
; Read access Write access CINH PLC-STOP No transfer Scaling factor: 10000
Parameter | Name:
C13037 | Actual speed DFIN
Data type: INTEGER_32
Index: 11538
d
= 2D12
h
Display range (min. value | unit | max. value)
-214748.3647 Unit/s 214748.3647
; Read access Write access CINH PLC-STOP No transfer Scaling factor: 10000
Parameter | Name:
C13040 | Resp. to track monitoring DFIN
Data type: UNSIGNED_8
Index: 11535
d
= 2D0F
h
Digital frequency extension module in module receptacle MXI1:
Response when track monitoring is triggered for digital frequency input X9
Track monitoring is triggered if a signal cable (A, B, or Z) is interrupted.
Selection list
(Lenze setting in bold)
1Fault
2Trouble
3 Quick stop by trouble
5 Warning
4 Warning locked
6 Information
0 No response
; Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C13041 | Resp. to DFIN enable sig. miss.
Data type: UNSIGNED_8
Index: 11534
d
= 2D0E
h
Digital frequency extension module in module receptacle MXI1:
Response when "Enable" signal at digital frequency input X9 fails
Selection list
(Lenze setting in bold)
1Fault
2Trouble
3 Quick stop by trouble
5 Warning
4 Warning locked
6 Information
0 No response
; Read access ; Write access CINH PLC-STOP No transfer