Digital frequency extension module | Parameter setting & configuration
Digital frequency input
Parameter setting
14 L EDS94AYFLF EN 3.2 - 10/2010
2.2.5 Voltage control - TTL encoder
If a TTL encoder is connected as the signal source and C13010
/ C14010 is set to TTL
encoder, the encoder can be supplied with a controlled +5 V voltage via pin 4, which serves
to compensate the voltage drop on the encoder cable.
2.2.6 Monitoring
Initialisation time
In C13013
/ C14013 an initialisation time can be set, which must elapse after starting the
system before the monitoring modes are switched active.
Thanks to this "delay" other system parts which serve as signal sources, can initialise
themselves first without monitoring being triggered due to missing signals.
In the "0" setting the initialisation time is set to infinity so that monitoring is
deactivated permanently.
If the setting is changed from "0" to another value, the initialisation time is restarted.
A higher-level control can, for instance, switch monitoring active by a corresponding
parameter setting of C13013
/ C14013 even if the device has been switched on for a
long time.
Monitoring of the +5 V voltage for the encoder
If an encoder is connected to X9 and supplied by the digital frequency extension module
"in a controlled way", the pin 8 of the digital frequency input X9 serves to control and
monitor the +5 V encoder voltage.
If the voltage control is not able to compensate the voltage drop, a fault message is
created and the response set in C13042
/ C14042 is executed.
At the same time the output DFIN_bVccCtrlLimited of the system block
LS_DigitalFrequencyInput is set to TRUE.
Stop!
If an encoder is connected to X9 and supplied by the digital frequency extension
module "in a controlled way", the pin 8 of the digital frequency input X9 serves
to control and monitor the +5 V encoder voltage. Monitoring
In this case, no digital signal ("Lamp control" or "Enable") may be supplied to PIN
8!
Please also observe the documentation for the encoder used.