6 Planning the CANopen network
6.3 Device specifications of the field devices
31
Lenze · Controller-based Automation · CANopen® Communication Manual · DMS 6.3 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3.3 Special features of the I/O system 1000 (EPM-Sxxx)
Basic identifier - I/O system 1000 (EPM-Sxxx)
The default setting of the basic identifier is as follows:
1) When creating the sync transmit/receive identifier manually, observe the use of the emergency telegram because
of the same COB-ID.
Object Direction Basic identifier
from the drive to the drive Dec hex
NMT 0 0x000
Sync 1) 128 0x080
Emergency 128 0x080
PDO1
(Process data channel 1)
TPDO1
384 0x180
RPDO1
512 0x200
PDO2
(Process data channel 2)
TPDO2
640 0x280
RPDO2
768 0x300
PDO3
(Process data channel 3)
TPDO3
896 0x380
RPDO3
1024 0x400
PDO4
(Process data channel 4)
TPDO4
1152 0x480
RPDO4
1280 0x500
PDO5
(Process data channel 5)
TPDO5
1664 0x680
RPDO5
1920 0x780
PDO6
(Process data channel 6)
TPDO6
448 0x1C0
RPDO6
576 0x240
PDO7
(Process data channel 7)
TPDO7
704 0x2C0
RPDO7
832 0x340
PDO8
(Process data channel 8)
TPDO8
960 0x3C0
RPDO8
1088 0x440
PDO9
(Process data channel 9)
TPDO9
1216 0x4C0
RPDO9
1344 0x540
PDO10
(Process data channel 10)
TPDO10
1728 0x6C0
RPDO10
1984 0x7C0
SDO1
(Parameter data channel 1)
TSDO1
1408 0x580
RSDO1
1536 0x600
Node guarding 1792 0x700