5 Installation
5.2 Electrical installation
32
Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Assignment of the X245 plug connector
Terminal data
Designation Description
+ U = 24 V DC (20.4 V - 0 % ... 28.8 V + 0 %)
I = 140 mA
- Reference potential for the external voltage supply
Area Values
Electrical connection 2-pole plug connector with spring connection
Possible connections Fixed:
0.2 ... 1.5 mm
2
(AWG 24 ... 16)
Flexible:
Without wire end ferrule
0.2 ... 1.5 mm
2
(AWG 24 ... 16)
With wire end ferrule, without plastic sleeve
0.2 ... 1.5 mm
2
(AWG 24 ... 16)
With wire end ferrule, with plastic sleeve
0.2 ... 1.5 mm
2
(AWG 24 ... 16)
Stripping length 10 mm