System bus (CAN) for Lenze PLC devices
Configuration (CAN−AUX interface)
6−13
l
PLC−Systembus EN 2.0
6.11.3 Bus load by CAN−AUX
Via C2461 you can receive a percentage display of the extent to which the system bus is loaded by
the telegrams of the CAN−AUX interface.
· Only valid telegrams are considered.
· Each transmit and receive channel is evaluated separately.
Code LCD
Possible settings
Information
Lenze Selection
C2461 Load IN/OUT
g
0 {1 %} 100 System bus − bus load
(CAN−AUX)
· Trouble−free operation demands
that the total bus load (all
connected devices) does not
exceed 80 %.
1 Message OUT All sent
2 Message IN All received
3 Message OUT1 Sent on CANaux_OUT1
4 Message OUT2 Sent on CANaux_OUT2
5 Message OUT3 Sent on CANaux_OUT3
6 Message POUT1 Sent on parameter data channel 1
7 Message POUT2 Sent on parameter data channel 2
8 Message IN1 Received from CANaux_IN1
9 Message IN2 Received from CANaux_IN2
10 Message IN3 Received from CANaux_IN3
11 Message PIN1 Received from parameter data
channel 1
12 Message PIN2 Received from parameter data
channel 2
Vista de pagina 86