System bus (CAN) for Lenze PLC devices
General information
2−11
l
PLC−Systembus EN 2.0
2.7 Transmitting parameter data
For Lenze devices, parameter data are the so−called codes.
· Parameter settings for instance are carried out in the case of a one−time setting of the system
during commissioning, or in the case of a material change of the production machine.
· Parameter data are transferred as so−called SDOs (Service Data Objects) via the system bus
and are acknowledged by the receiver, i. e. the transmitter receives a feedback on whether the
transmission was successful.
2.7.1 Parameter data telegram
The telegram for parameter data is structured as follows:
11bit 8 bytes user data
Identifier
Command
code
Index
Subindex Data 1 Data 2 Data 3 Data 4
Low byte High byte
· In the following subchapters the different components of the telegram are explained in detail.
· An example for writing a parameter can be found in chapter 2.7.2. (^ 2−15)
· An example for reading a parameter can be found in chapter 2.7.3. (^ 2−17)
2.7.1.1 Identifier
Identifier
Command
code
Index
Subindex Data 1 Data 2 Data 3 Data 4
Low byte High byte
For the transmission of parameter data, two parameter data channels are provided, which are
addressed via the identifier:
Identifier = basic identifier + node address of the node
dec hex
SDOs Parameter data channel 1
Output (transmission) 1536 600
+ C0350
+ C2350
+ C2450
(CAN)
(XCAN)
(FIF−CAN/CANaux)
Input (reception) 1408 580
Parameter data channel 2
Output (transmission) 1600 640
+ C0350
+ C2350
+ C2450
(CAN)
(XCAN)
(FIF−CAN/CANaux)
Input (reception) 1472 5C0
Tip!
Between the identifiers for parameter data channels 1 and 2 there respectively is an offset of 64:
· Output of parameter data channel 1 = 1536
· Output of parameter data channel 2 = 1536 + 64 = 1600