System bus (CAN) for Lenze PLC devices
CAN system blocks
7.6 CAN_Management (node number: 101)
7−21
L
PLC−Systembus EN 2.0
7.6.2 Outputs_CAN_Management
Variable Data type Signal type Address Display
code
Display
format
Notes
CAN_bResetNode_b
Bool Binary
%QX101.0.0
Carry out reset node of the PLC
CAN_bTxCan2Synchronized_b %QX101.0.1 Transmit CAN2_OUT with sync
telegram.
CAN_bTxCan3Synchronized_b %QX101.0.2 Transmit CAN3_OUT with sync
telegram.
Note!
If CAN_bTxCan2Synchronized_b and/or CAN_bTxCan3Synchronized_b are integrated, it is required
to configure the device as sync transmitter. The data are transmitted immediately after the sync
signal is sent.
7.6.3 Activating a reset node
A reset node is activated by setting CAN_bResetNode_b to TRUE or C0358 = 1.
Tip!
Even if the CAN_Management SB has not been assigned to the control configuration, a reset node
can be activated via C0358.
(^ 3−8)
7.6.4 Defining the instant of transmission for CAN2_OUT/CAN3_OUT
Via CAN_bTxCan2Synchonized_b and CAN_bTxCan3Synchonized_b you define the instant of
transmission for the CAN objects CAN2_OUT and CAN3_OUT:
· FALSE: Data from CAN2_OUT/CAN3_OUT are sent at the end of the process image.
· TRUE: Data from CAN2_OUT/CAN3_OUT are sent to sync.
The identifiers for the sync transmission C0369 and reception telegram can be set via
C0367/C0368.
The sync Tx time can be set via C0369.
Detailed information on this can be found in the description of the CAN_Syncronization SB.
(^ 7−23)