System bus (CAN) for Lenze PLC devices
"CAN" system bus interface configuration
3−14
l
PLC−Systembus EN 2.0
3.13.2 Telegram counter
Via C0360 you can have the number of the telegrams sent and received by the PLC via
CAN1_IO ... CAN3_IO displayed.
· Only the telegrams which are valid for the PLC are counted.
· Each transmit and receive channel is evaluated separately.
· The max. counter content is 65535 (16 bit); if this value is exceeded, the corresponding
counter starts with 0 again.
Code LCD
Possible settings
Information
Lenze Selection
C0360 CAN message
g
0 {1} 65535 System bus telegram counter
(number of telegrams)
· For values > 65535 counting
restarts with 0.
1 Message OUT All sent
2 Message IN All received
3 Message OUT1 Sent on CAN_OUT1
4 Message OUT2 Sent on CAN_OUT2
5 Message OUT3 Sent on CAN_OUT3
6 Message POUT1 Sent on parameter data channel 1
7 Message POUT2 Sent on parameter data channel 2
8 Message IN1 Received from CAN_IN1
9 Message IN2 Received from CAN_IN2
10 Message IN3 Received from CAN_IN3
11 Message PIN1 Received from parameter data
channel 1
12 Message PIN2 Received from parameter data
channel 2