System bus (CAN) for Lenze PLC devices
"CAN" system bus interface configuration
3−13
l
PLC−Systembus EN 2.0
3.13 Diagnostics
The following codes can be used for diagnostics purposes:
Code Information displayed Information
C0359 Operating status of the system bus Chapter 3.13.1 ^ 3−13
C0360 Number of the telegrams sent and received Chapter 3.13.2 ^ 3−14
C0361 Bus load (in %) Chapter 3.13.3 ^ 3−15
· Settings cannot be carried out via these codes.
3.13.1 Operating status of the CAN interface
Via C0359 you can have the operating status of the system bus displayed:
Code LCD
Possible settings
Information
Lenze Selection
C0359 CAN state
g
0 Operational
1 Pre−operational
2 Warning
3 Bus off
System bus status
C0359 Operating status Information
0 Operational The system bus is fully functional. The PLC can transmit and receive parameter and process data.
1 Pre−operational The PLC can transmit and receive parameter data. Process data, however, are ignored.
A status change from Pre−operational to Operational can be effected by:
· the CAN master ^ 3−2
· a reset node
– via C0358, if the PLC has been configured as a "quasi" master. ^ 3−8
– via the binary input signal "reset node" at the CAN_Management SB ^ 7−20
2 Warning The PLC has received faulty telegrams and is only involved in the system bus passively, i. e. no data can be
sent from the PLC anymore.
Possible causes:
· Missing bus termination
· Non−sufficient shielding
· Differences in potential with regard to the earth connection of the control electronics
· Bus load too high
· PLC is not connected to the system bus.
3 Bus−off The PLC has disconnected from the system bus due to too many faultily received telegrams.
· The response to this status can be configured via C0595. ^ 3−11