Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17 87
13 Error messages
13.1 Short overview of the PROFIBUS error messages
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13 Error messages
This chapter supplements the error list for the Servo Drive 9400 contained in the software manual
and in the »Engineer« online help with the error messages of the communication module.
13.1 Short overview of the PROFIBUS error messages
The following table lists all PROFIBUS error messages in numerical order of the error number.
Furthermore the preset error response and – if available – the parameters for setting the error
response are specified.
Tip!
When you click the cross-reference in the first column, you will see a detailed description
(causes and remedies) of this error message.
Software manual/online help for Servo Drive 9400
Here you can find general information on diagnostics & fault analysis and on error
messages.
Error number Designation Response (Lenze setting) Adjustable in
hex dec
0x00c83100
13119744 Profibus: Lost connection to 9400 base device 0: No response -
0x00c85531
13129009 Profibus: No memory access 6: Information -
0x00c85532
13129010 Profibus: Read memory error 6: Information -
0x00c85533
13129011 Profibus: Write memory error 6: Information -
0x00c86010
13131792 Profibus: Restart after watchdogreset 1: Fault -
0x00c86011
13131793 Profibus: Internal error 1: Fault -
0x00c86100
13132032 Profibus: Internal error 0: No response -
0x00c86101
13132033 Profibus: Internal error 1: Fault -
0x00c86110
13132048 Profibus: Internal mapping error 4: Warning locked -
0x00c8641f
13132831 Profibus: Invalid parameter record 1: Fault -
0x00c86420
13132832 Profibus: Error: Lenze setting loaded 1: Fault -
0x00c88130
13140272 Profibus watchdog: Monitoring time elapsed 0: No response C13880/1
C14880/1
0x00c88131 13140273 Profibus: Data_Exchange state exited 0: No response C13880/1
C14880/1
0x00c88132 13140274 Profibus watchdog: DP-V1 MSAC2 elapsed 0: No response C13880/2
C14880/2
Comentarios a estos manuales