Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17 15
4Technical data
4.1 General data and operating conditions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4 Technical data
4.1 General data and operating conditions
"Servo Drives 9400" Hardware Manual
Here you can find the ambient conditions and information on the electromagnetic
compatibility (EMC) which also apply to the communication module.
Area Values
Order designation E94AYCPM
Communication profile • PROFIBUS DP-V0 (DRIVECOM)
• PROFIBUS DP-V1 (PROFIdrive)
Communication medium RS485
Interface 9-pin Sub-D socket
Network topology • Line (without repeater)
• Tree/line (with repeater)
Bus device type PROFIBUS slave
Number of slaves • Max. 31 (without repeater)
• Max. 125 (with repeater)
Max. cable length 1200 m (depending on the selected baud rate and the cable type used)
PNO identification number 0x07A8
Baud rate for cable type A (EN 50170) 9.6 kbps ... 12 Mbps (automatic detection)
Voltage supply External supply via the 2-pin plug connector
• Terminal "+": U = 24 V DC (20.4 V - 0 % ... 28.8 V + 0 %), I = 130 mA
• Terminal "-": Reference potential for external voltage supply
Conformities, approvals • CE
•UL