14 Parameter reference
14.3 Parameters of the communication module for slot MXI2
106
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14867
C14868
C14880
Parameter | Name:
C14867 | Display: Most recent diagnostic data
Data type: OCTET_STRING
Index: 9708
d
= 25EC
h
Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)
Advanced diagnostic message
( 85)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14868 | Display: DP state
Data type: UNSIGNED_8
Index: 9707
d
= 25EB
h
Available from software version 01.21!
Display of the DP states (Decentralized Peripherals)
Short-time interruption of PROFIBUS communication
( 79), see fig. [11-1]
Selection list (read only)
0 Waiting for parameterisation
1 Waiting for configuration
2 Data exchange
3 n/a
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14880 | Reaction on communication fault
Data type: UNSIGNED_8
Index: 9695
d
= 25DF
h
Monitoring response to a communication fault on the PROFIBUS
A change in the monitoring response is effective immediately.
Permanent interruption of PROFIBUS communication
( 78)
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
Subcodes Lenze setting Info
C14880/1 0: No response The response set here for the "Watchdog/Data
Exchange" monitoring function is executed if the bus
station ...
• does not receive a message from the master within
the watchdog monitoring time (displayed in C14882/
1) if there is an active connection.
• detects that it is no longer in the "DATA_EXCHANGE"
status. Please see also the notes given under C14881
.
C14880/2 0: No response The response set here for the "DPV1 MSAC2" monitoring
is executed if the bus station does not receive a "DPV1
MSAC2" message from the master within the monitoring
time (displayed in C14882/2
) if there is an active
connection) and the MSAC2 connection is stopped by the
slave.
Note: We recommend only setting "information" as
response so that no drive-relevant response is executed.
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT