Lenze E94AYCPM Manual de usuario Pagina 33

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 125
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 32
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17 33
6 Commissioning
6.4 First switch-on
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4 First switch-on
Documentation for the standard device
Observe the safety instructions and residual hazards stated.
Note!
Establishing communication
In order to establish communication via an externally supplied communication module,
the standard device must be switched on as well.
After communication has been established, the externally supplied module operates
independently of the power on/off state of the standard device.
Protection against uncontrolled restart
After a fault (e.g. short-time mains failure), the restart of a drive is not always wanted
and - in some cases - even not allowed.
In the Lenze setting of the Servo Drives 9400, the restart protection is activated.
Via C00142 ("Auto-restart after mains connection"), you can configure the restart
behaviour of the controller:
C00142 = "0: Inhibited" (Lenze setting)
The controller remains inhibited (even if the fault is no longer active).
The drive starts in a controlled mode by explicitly enabling the controller: LOW-HIGH
edge at digital input X5/RFR.
C00142 = "1: Enabled"
An uncontrolled restart of the drive is possible.
Vista de pagina 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 124 125

Comentarios a estos manuales

Sin comentarios