Communication manual 8400 motec PROFINET
Parameter reference
Parameters relevant for PROFINET communication
82 L EDS84DMOTPNET EN 2.0 - 11/2011
C13887
C13899
C13900
Parameter | Name:
C13887 | Suppress signalling diag. mess. upon
Data type: BITFIELD_8
Index: 10688
d
= 29C0
h
This code serves to inhibit the transmission of alarm messages to the IO controller. By this, errors of a specific type
can be systematically suppressed. All errors are furthermore entered in the logbook.
A change will only become effective immediately if no error number with the error type selected here is pending
in C00165.
Value is bit-coded: Info
Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Station name
Data type: VISIBLE_STRING
Index: 10676
d
= 29B4
h
The name with a max. length of 240 characters is distributed to the subindices. The name can be entered starting
with subindex 1. The following unused subindices are not relevant.
The station name must be assigned in accordance with the PROFINET specification. In the standard setting a
deleted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an
IO supervisor or an I/O controller.
A change of the station name will only become effective by switching the mains of the controller.
Setting the station name
( 28)
Subcodes Lenze setting Info
C13899/1 1st ... 30th character
C13899/2 31th ... 60th character
C13899/3 61th ... 90th character
C13899/4 91th ... 120th character
C13899/5 121th ... 150th character
C13899/6 151th ... 180th character
C13899/7 181th ... 210th character
C13899/8 211th ... 240th character
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13900 | Firmware product type
Data type: VISIBLE_STRING
Index: 10675
d
= 29B3
h
The code contains a string with a length of 8 characters. The identification code "E84DGFCR" is output.