Communication manual 8400 motec PROFINET
Commissioning
Setting the station name
28 L EDS84DMOTPNET EN 2.0 - 11/2011
6.3 Setting the station name
The station name currently used is shown in code C13864
.
The station name ...
is required for unambiguous addressing of the Inverter Drive 8400 motec by the I/O
controller.
can either be assigned by the I/O controller via PROFINET or set manually in the
»Engineer«.
has to be allocated in accordance with the PROFINET specification:
1 or several labels separated by ".".
Max. length per label: 63 characters
Max. total length: 240 characters
Permissible characters: [a ... z], [0 ... 9], [.], [-]
Labels must not begin or end with [-].
Prohibited syntax:
"n.n.n.n" (n = 0 ... 999)
"port-xyz" (x,y,z=0...9)
"port-xyz-abcde" (a,b,c,d,e,x,y,z=0...9)
Note!
The "Node blinking test" PROFINET function which serves to identify an
accessible device is supported. The red LED BE (LED status displays
( 64))
flickers during execution.
Operation on the PROFINET requires a valid station name.
In the case of impermissible settings, the red LED BE blinks (LED status
displays ( 64)), and the error message PROFINET: Stack init error
[0x01bc6534] ( 72) is output. The Communication Unit then internally
continues to work with the deleted name.
If the station name is assigned by the IO controller via PROFINET or the
PROFINET configurator of the »Engineer«, changes will be effective
immediately.