EDS84DMOTPNET EN 2.0 - 11/2011 L 71
Communication manual 8400 motec PROFINET
Error messages
Possible causes and remedies
PROFINET: Record Parameter: Invalid read [0x01bc6501]
PROFINET: Record Parameter: Invalid write [0x01bc6502]
PROFINET: Data output status bad [0x01bc6503]
PROFINET: Data_Exchange status quit [0x01bc6531]
PROFINET: Station name error [0x01bc6532]
PROFINET: IP address error [0x01bc6533]
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
Invalid parameter read access Check configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
Invalid parameter write access
When reading back data, the IO controller requested a
too short data length (number of data bytes).
Check configuration.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
Output data invalid.
Connection to Siemens S7 has been interrupted.
Check cables and terminals.
Connect network cable to PROFINET connections.
Response (Lenze setting printed in bold) Setting: C13880/1 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
The data exchange via PROFINET has been terminated.
See also chapter "Interruption of PROFINET
communication" ( 62).
Check cables and terminals.
Connect network cable to PROFINET connections.
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Station name is not DNS-conform. Use DNS-conform station name.
Setting the station name
( 28)
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid IP address has been assigned by the I/O
controller via PROFINET or has been set in code C13000
.
Make sure that the I/O controller has assigned a valid
IP address via PROFINET.
Set a valid IP address.
Setting the IP configuration
( 30)