Communication manual 8400 motec PROFINET
Process data transfer
Process input data AI/DI (Slot2)
44 L EDS84DMOTPNET EN 2.0 - 11/2011
8.3 Process input data AI/DI (Slot2)
0, 1, or 2 input words can be optionally assigned to slot 2.
The data represent the states of the digital inputs (RFR, DI1 ... DI5) and the analog input
of the device.
Via the fieldbus these data can even be read when no mains voltage is applied to the
Communication Unit and only the fieldbus interface connection is supplied with
24 V DC.
Data word Bits Function Value / description
Word 1 0
...
9
Analog input value
(0 ... 10 V)
10 V = 1000
10 Digital input 3 0 (FALSE) Open
1 (TRUE) Closed
11 Digital input 4 0 (FALSE) Open
1 (TRUE) Closed
12 Digital input 5 0 (FALSE) Open
1 (TRUE) Closed
13 Reserved
14 I/O status 0 (FALSE) Data in word 1/2 are not valid.
1 (TRUE) Data in word 1/2 are valid.
15 Connection status of the
controller
0 (FALSE) Controller is offline ("Stay alive" operation)
1 (TRUE) Controller is online
Word 2 0 RFR 0 (FALSE) Open
1 (TRUE) Closed
1 Digital input 1 0 (FALSE) Open
1 (TRUE) Closed
2 Digital input 2 0 (FALSE) Open
1 (TRUE) Closed
3 Digital input 3 0 (FALSE) Open
1 (TRUE) Closed
4 Digital input 4 0 (FALSE) Open
1 (TRUE) Closed
5 Digital input 5 0 (FALSE) Open
1 (TRUE) Closed
6
...
13
Reserved
14 I/O status 0 (FALSE) Data in word 1/2 are not valid.
1 (TRUE) Data in word 1/2 are valid.
15 Connection status of the
controller
0 (FALSE) Controller is offline ("Stay alive" operation)
1 (TRUE) Controller is online