Communication manual 8400 motec PROFINET
Parameter data transfer
Writing parameters to the controller
58 L EDS84DMOTPNET EN 2.0 - 11/2011
Parameter response after a correct write request
Parameter response after write error
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Response identification Axis Number of indices
0xXX 0x02 0x00 0x01
(mirrored) Parameters written (mirrored) 1 index
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Response identification Axis Number of indices
0xXX 0x82 0x00 0x01
(mirrored) Parameters not written (mirrored) 1 index
Byte 5 Byte 6
Format Number of values
0x44 0x01
Error Error code without additional
information
Byte 7 Byte 8
Error code
High byte Low byte
For meaning see chapter "Error information (error)"
( 59)