EDS94TA10030xxxx EN 1.2 - 11/2009 L 33
9400 Technology applications | Electronic gearbox
Short setup
Step 5: Controlling applications via terminals
4.7 Step 5: Controlling applications via terminals
Terminal assignment
Procedure
1. Enable controller: Set digital input RFR to HIGH level.
2. Deactivate quick stop: Set digital input DI1 to HIGH level.
Terminal Assignment (Lenze setting)
X5 RFR Controller enable
DI1 Quick stop
If DI1 is set to LOW level, the drive is decelerated to standstill within the deceleration
time set for the quick stop function independent of the setpoint selection.
If the quick stop function is deactivated, the drive is led to the selected setpoint again via
the set acceleration time.
DI2 Connection of reference switch
DI3 -
DI4 Close clutch
DI5 Reset error
By means of a LOW-HIGH edge an existing error status can be reset if the cause of the
fault is removed.
DI6 -
DI7 -
DI8 -