Lenze c300 Manual de usuario Pagina 181

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 195
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 180
13 Parameter reference
13.9 Communication cards: optional interface
181
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C1082
C1090
C1091
C1092
Parameter | Name:
C1082 | Baud rate
Data type: UNSIGNED_32
Index: 23493
d
= 5BC5
h
Baud rate of the CAN interface. The value is assigned from a selection list.
Selection list (Lenze setting printed in bold)
75
610
520
350
8 100
2 125
1 250
0 500
4 1000
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1090 | Tx PDO counter
Data type: UNSIGNED_32
Index: 23485
d
= 5BBD
h
PDO counter for sent CAN messages
Display range (min. value | unit | max. value)
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1091 | Rx PDO counter
Data type: UNSIGNED_32
Index: 23484
d
= 5BBC
h
PDO counter for received CAN messages
Display range (min. value | unit | max. value)
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1092 | Bus load
Data type: UNSIGNED_32
Index: 23483
d
= 5BBB
h
Specification of the average bus load. The bus load is calculated as follows: Bus load = Value in percent x 1000
Display range (min. value | unit | max. value)
Read access Write access CINH PLC-STOP No transfer
Vista de pagina 180
1 2 ... 176 177 178 179 180 181 182 183 184 185 186 ... 194 195

Comentarios a estos manuales

Sin comentarios