66 L PM94H201B_13xxxxxx_EN
Programming
2.15.9.8 Homing Method 8: Homing on the Home Switch & Index Pulse
Using this method the initial direction of movement is negative (if the homing switch is active). The home position is the
first index pulse to the positive side of the position where the homing switch becomes inactive.
Axis will accelerate to fast homing velocity in the negative direction and continue until Homing Switch (selectable via
Var_Home_Switch_Input Variable) is deactivated (falling edge) shown at position A. Axis then decelerates to zero
velocity.
If the homing switch is already inactive when the homing routine commences then this initial move is not executed.
Axis will then accelerate to fast homing velocity in the positive direction. Motion will continue until first the rising edge
of the Homing switch is detected (position B) and then the rising edge of the first index pulse (position 8) is detected.
NOTE: if the axis is on the wrong side of the homing switch when homing is started then the axis will move positive until
it contacts the positive limit switch (A2). Upon activating the positive limit switch the axis will change direction (negative)
following the procedure as detailed above.
A
B
8
8
B
Index Pulse
(via Input C3)
Homing Switch
(Var_Home_Switch_Input)
Figure 32: Homing Method 8