
12 Error messages
12.2 Possible causes and remedies
52
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
INTERBUS: Invalid initialisation [0x00c88127]
INTERBUS: Data exchange stopped [0x00c88131]
INTERBUS: Received process data length is contradictory [0x00c88211]
INTERBUS: Process data length to be sent is contradictory [0x00c88212]
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
The INTERBUS initialisation has failed. Execute renewed initialisation by the master.
Response (Lenze setting printed in bold) Setting: C13880/1 / C14880/1
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Data exchange via INTERBUS has been stopped. • Check cables and terminals.
• Execute renewed initialisation by the master.
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
The number of received I/O data via INTERBUS (display in
C13860/2
/ C14860/2) does not correspond to the
number configured by the device through port mapping
(display in C13854/1
/ C14854/1).
The data word sum (process data word + parameter data
words) has to consist of 1 ... 10 words (16 bits/word).
Check whether the differing data length is sufficient for
the application.
If required, adapt the port mapping or the I/O data
length of the received data.
Configuring process data (PDO mapping)
( 37)
Setting the number of process data words
( 31)
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
The number of I/O data to be sent via INTERBUS (display
in C13860/2
/ C14860/2) does not correspond to the
number configured by the device through port mapping
(display in C13855/1
/ C14855/1).
The data word sum (process data word + parameter data
words) has to consist of 1 ... 10 words (16 bits/word).
Check whether the differing data length is sufficient for
the application.
If required, adapt the port mapping or the I/O data
length of the data to be sent.
Configuring process data (PDO mapping)
( 37)
Setting the number of process data words
( 31)
Comentarios a estos manuales