6 Commissioning
6.2 Possible settings via DIP switch
30
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2 Possible settings via DIP switch
[6-1] DIP switch
E94YCIB001D
The following can be set via the S205 DIP switch:
Number of the process data words
switches: 1 ... 4
( 31)
Number of the parameter data words
switches: 5 and 6
( 32)
•Baud rate
switch: 8
( 33)
Lenze setting: All switches "OFF"
Switch 7 has no function.
Note!
All DIP switches = "OFF" (Lenze setting):
At switch-on, the configuration from the codes gets active (Settings in »Engineer«
( 34)
).
At least one DIP switch = "ON":
At switch-on, the values are accepted from the switch positions.
The data word sum (process data words + parameter data words) has to consist of
1 ... 10 words (16 bits/word).
Switch off the voltage supply of the communication module and afterwards on again
to activate changed settings.