6 Commissioning
6.2 Possible settings via DIP switch
32
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.2 Setting the number of parameter data words
• The number of parameter data words can be set via the switches 5 and 6.
• 0, 1, 2 order 4 parameter data words can be used.
• The current setting is displayed in the »Engineer« in C13860/1
/ C14860/1.
Note!
The data word sum (process data word + parameter data words) has to consist of 1 ... 10
words (16 bits/word).
Impermissible settings are reported by the BE LED (red blinking).
LED status displays
( 47)
The communication module then operates internally with the following values:
• 2 process data words (PD)
• 1 parameter data word (PCP)
DIP switch Number of PCP Switch Max. number of
PD
ID code
[hex]
5 6
0OFFOFF100x03
1OFFON 90xE3
2 ON OFF 8 0xE0
4 ON ON 60xE1