Lenze E94AYCIB Manual de usuario Pagina 33

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 78
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 32
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 33
6 Commissioning
6.2 Possible settings via DIP switch
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.3 Setting the baud rate
The baud rate can be set via the switch 8.
Set the baud rate according to the length of the bus cable between the single INTERBUS nodes.
The current setting is displayed in the »Engineer« in C13863
/ C14863.
Note!
Select the baud rate which depends on the data volume, cycle time, and number of
nodes just high enough to suit your application.
DIP switch Switch 8 Baud rate Cable length between adjacent nodes
OFF 500 kbps max. 400 m
ON 2 Mbps max. 150 m
12345678
ON
OFF
Vista de pagina 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 77 78

Comentarios a estos manuales

Sin comentarios