Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 33
6 Commissioning
6.2 Possible settings via DIP switch
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.3 Setting the baud rate
• The baud rate can be set via the switch 8.
• Set the baud rate according to the length of the bus cable between the single INTERBUS nodes.
• The current setting is displayed in the »Engineer« in C13863
/ C14863.
Note!
Select the baud rate which depends on the data volume, cycle time, and number of
nodes just high enough to suit your application.
DIP switch Switch 8 Baud rate Cable length between adjacent nodes
OFF 500 kbps max. 400 m
ON 2 Mbps max. 150 m