5 Installation
5.2 Electrical installation
26
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Assignment of the 9-pole Sub-D socket X207 (OUT)
5.2.4 Dimensions of 9-pole sub-D connectors
[5-6] Dimensions of 9-pole sub-D connectors
Pin Name Input/output Description
1 DO2 Output RS485: DO2 not inverted
2 DI2 Input RS485: DI2 not inverted
3GND Reference potential
4GND
5Vcc5 Output 5 V DC
6/DO2 Output RS485: DO2 inverted
7 /DI2 Input RS485: DI2 inverted
8Vcc5 Output 5 V DC
9 RBST Signalling input Connection to the outgoing INTERBUS is plugged.
Note!
Comply with the dimensions for width and depth of the 9-pole Sub-D connectors for the
INTERBUS terminals X206/X207.
E94YCIB001G