Lenze E84DxxxxxxxxxR Manual de usuario Pagina 14

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 84
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 13
Communication manual 8400 protec PROFINET
Technical data
Communication time
14 L EDS84DPNET EN 4.0 - 11/2010
3.3 Communication time
The communication time is the time between the start of a request and the arrival of the
corresponding response.
The communication times in the PROFINET network depend on the ...
Processing time within the drive controller;
Telegram runtime (baud rate / telegram length);
Nesting depth of the network.
Processing time inside the controller
There are no interdependencies between parameter data and process data.
Data Processing time
Process data Approx. 2 ms
+ 0 ... 1 ms
+ 1 ... x ms
Update cycle
Processing time in the controller
Runtime of the application task of the technology
application used (tolerance)
Parameter data Approx. 30 ms + a tolerance of 20 ms (typically)
Some codes may require a longer processing time.
Vista de pagina 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 83 84

Comentarios a estos manuales

Sin comentarios