Function library
Working with function blocks
3.1.1 Signal types
3−5
l
EDSVS9332K−EXT EN 4.0
3.1 Working with function blocks
The signal flow of the controller can be configured by connecting function blocks. The controller can
thus be easily adapted to diverse applications.
3.1.1 Signal types
Each function block is provided with a certain number of inputs and outputs which can be interlinked.
Corresponding to their functions, there are only certain types of signals at the inputs and outputs:
l Quasi analog signals
Symbol:
Unit: %
Designation: a
Value range: ±16384 = ±100 %
Resolution: 16 bits, scaling ±16384 ¢ ±100 %
l Digital signals
Symbol:
Unit: binary, with HIGH or LOW level
Designation: d
Resolution: 1 bit
l Speed signals
Symbol:
Unit: rpm (for display, internal representation in [inc/ms])
Designation: phd
Value range: ±2
15
− 1
Resolution: 16 bits
l Angle signals
Symbol:
Unit: inc
Designation: ph
Value range: ±2
31
− 1
Resolution: 32 bits, scaling 1 revolution ¢ 65536 inc
Only the same signal types can be connected. Thus, an analog output signal of one function block
can only be connected to the analog input of the other function block. If you try to connect two
different signal types, the connection is rejected.