2.5 EN - 01/2012 L 73
Industrial PC | Parameter setting & configuration
IPC backup & restore
Software update procedure
9.7 Software update procedure
Steps to be carried out in the case of R1.5:
How to identify the currently installed version:
In the web-based parameterisation the software version can be found under:
Parameter list 1 -> Device: Software version
The first two version numbers are important.
Carrying out a SW update of R1.5
When you install an update of R1.5, e. g. to R2.0, you have to carry out the following steps:
How to carry out an R1.5 software update:
1. Prepare USB stick for an update with »IPC Backup & Restore« under Windows® XP.
2. Connect USB stick to the running Industrial PC
3. Copy the BackupRestoreX86Rel.Cab from directory
\USBStorage\<UpdatePaket>\CAB\ BackupRestoreX86Rel.Cab
to
\Storage\BackupRestoreX86Rel.Cab under Windows® CE.
4. Remove USB stick.
5. Restart Industrial PC.
By this the new runtime environment is extracted.
6. Restart Industrial PC with the USB stick prepared.
Note!
Lenze recommend archiving the Compact Flash card using »IPC Backup &
Restore« under Windows® XP before carrying out a software update.