Industrial PC | Parameter setting & configuration
Parameter reference
Industrial PC extension modules
202 L 2.5 EN - 01/2012
C1596/19
AL status codes
Parameter | Name:
C1596/19 | ECAT: Error code
Data type: UNSIGNED_32
Index: 22979.19
d
=
0x59C3.0x13
h
Display of the AL status code (slave register "0x0134 : 0x0135")
; Read access Write access CINH PLC STOP No transfer
Code (hex) Description Current state or state
change
Resulting state
0x0000 No error Arbitrary Current state
0x0001 Unspecified error Arbitrary Arbitrary + E
0x0011 Invalid requested state IS, IO, PO, OB,
SB, PB
Current state + E
0x0012 Unknown requested state Arbitrary Current state + E
0x0013 Bootstrap state is not supported IBI + E
0x0014 Invalid Firmware IPI + E
0x0015 Invalid mailbox configuration IBI + E
0x0016 Invalid mailbox configuration IPI + E
0x0017 Invalid sync manager configuration PS, SO Current state + E
0x0018 No valid inputs available O, S, PSP + E
0x0019 No valid outputs available O, SOS + E
0x001A Synchronisation error O, SOS + E
0x001B Sync manager watchdog O, S S + E
0x001C Invalid sync manager types O, S S + E
PSP + E
0x001D Invalid output configuration O, S S + E
PSP + E
0x001E Invalid input configuration O, S, PSP + E
0x001F Invalid watchdog configuration O, S, PSP + E
0x0020 Slave requires 'cold boot' Arbitrary Current state + E
0x0021 Slave requires 'Initialisation' state B, P, S, O Current state + E
0x0022 Slave requires 'Pre-Operational' state S S + E
OO + E
0x0023 Slave requires 'Safe Operational' state O O + E
0x0030 Invalid DC configuration O, S S + E
0x0031 Invalid DC latch configuration O, S S + E
0x0032 PLL error O, S S + E
0x0033 DC I/O error O, S S + E
0x0034 DC time-out error O, S S + E
0x0042 MBX_EOE B, P, S, O Current state + E
Legend:
I: Initialisation
B: Bootstrap (is not supported)
P: Pre-Operational
S: Safe Operational
O: Operational
E: Error-Flag