Control technology | PROFIBUS communication manual
Function libraries
BusDiag.lib function library
42 L DMS 2.2 EN 07/2011 TD17
Example: Diagnostics information of Servo Drives 9400 in ’EXTENDEDINFO’
EXTENDEDINFO
ARRAY [0...129]
OF BYTE
Contains the slave-specific diagnostics information.
Byte 0 Station status 1
Byte 1 Station status 2
Byte 2 Station status 3
Byte 3 Master station number
Byte 4 Manufacturer's identification mark (high byte)
Byte 5 Manufacturer's identification mark (low byte)
Byte 6 ... n Slave-specific diagnostics information (see documentation of the
slave)
Byte in
EXTENDEDINFO
Meaning
6 Bit 0: Station does not exist (set by the master).
Bit 1: Slave is not ready for data exchange.
Bit 2: Configuration data do not match each other.
Bit 3: Slave has extended diagnostic data.
Bit 4: Requested service is not supported by the slave.
Bit 5: Slave response is invalid (set by the master)
Bit 6: Incorrect parameter setting
Bit 7: Slave is parameterised by another master (set by the master).
7 Bit 0: Slave has to be parameterised again.
Bit 1: Static diagnostics
Bit 2: Fixedly set to "1".
Bit 3: Watchdog active
Bit 4: Freeze command received.
Bit 5: Sync command received.
Bit 6: Reserved
Bit 7: Slave is deactivated (set by the master).
8 Bit 7: Diagnostics overflow - amount of diagnostics data present in the slave is too large to fit
into one telegram.
9 Bits 0 ... 7: Master address after parameter setting ("0xFF" without parameterisation)
10 Bits 0 ... 7: ID number (high byte)
11 Bits 0 ... 7: ID number (low byte)
12 Header
The header contains the block length of extended diagnostics and the header byte.
In this case, the value of the entry is "0x0A" (bytes 6 ... 15 = 10 bytes).
13 Status_Type
The value of this entry is fixed. For the following bit assignment it is "0x81":
Bit 7 = 1: "status"
Bit 0 = 1: "status message"
Values of all other bits = 0
14 Slot_Number
Value of the slot number: "0x00"
15 Specifier
A detected error is entered in the specifier with the identification "0x0" (status coming).
An eliminated error is entered in the specifier with the identification "0x02" (status going).
If no errors are indicated, the entry in the specifier has the value "0x00" (no further
differentiation).
16 PROFIsafe, error number of the safety module
If an error occurs in the safety module, byte 10 (low byte) and byte 11 (high byte) contain the
corresponding error number.
More information can be found in the documentation of the corresponding safety module.
17
Identifier/data type Meaning/possible settings