Commissioning
Setting the node address
Settings by a master (class 2)
6
l 43
EDSMF2133IB EN 5.0
6.7.3 Settings by a master (class 2)
ƒ With this method only one device must be connected to the bus. This can be
achieved by a special switch−on sequence.
ƒ In the "Power On" status, the master (class 2) can set a device address via the
"Set_Slave_Address" telegram.
ƒ Settings made through the master (class 2 only) have an effect on the setting in
standard device code C0009.
PROFIBUS station address Mapping to code C0009
1 ... 2 No (master addresses)
3 ... 99 Yes (3 ... 99)
100 ... 125 Yes (C0009 = 2)
126 (LENZE setting) Yes (C0009 = 1)
Tab. 6−1 Assignment of station addresses to controllers