Lenze EMF2133IB Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 134
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Technical data
Protective insulation
4
l
17
EDSMF2133IB EN 5.0
4.2 Protective insulation
{ Danger!
Dangerous electrical voltage
If Lenze controllers are used on a phase earthed mains with a rated mains
voltage 400 V, protection against accidental contact is not ensured without
implementing external measures.
Possible consequences:
ƒ Death or serious injury
Protective measures:
ƒ If protection against accidental contact is required for the control terminals
of the controller and the connections of the plugged device modules, ...
– a double isolating distance must exist.
– the components to be connected must be provided with the second
isolating distance.
Insulation between bus and ... Type of insulation (in accordance with EN
61800−5−1)
l Reference earth / PE Functional insulation
l External supply Functional insulation
l Power section
820X / 821X Basic insulation
822X / 8200 vector Reinforced insulation
Drive PLC Reinforced insulation
93XX / 9300 Servo PLC Reinforced insulation
ECS servo system Reinforced insulation
l Control terminals
820X / 8200 vector Functional insulation
821X Functional insulation
822X Basic insulation
Drive PLC Basic insulation
93XX / 9300 Servo PLC Basic insulation
ECS servo system Reinforced insulation
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 133 134

Comentarios a estos manuales

Sin comentarios