Lenze E84AYCIB Manual de usuario Pagina 57

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 75
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 56
EDS84AYCIB EN 4.0 - 11/2010 L 57
E84AYCIB communication manual (INTERBUS)
Diagnostics
Querying the current bus status
11.2 Querying the current bus status
Code C13861
displays the current bus status of the INTERBUS node:
Diagnostics with the »Engineer«
In the »Engineer« the Diagnostics tab serves to display various pieces of diagnostic
INTERBUS information.
Value of C13861
[hex]
Bus status Description
0xyyy0 IBS-INIT Initialisation
0xyyy1 IBS-ACTIVE The bus is active. Data cycles are executed.
0xyyy2 IBS-READY The bus is ready for operation. No data cycles are executed.
yyy = device-internal use