E84AYCIB communication manual (INTERBUS)
Parameter data transfer
Supported PMS services
50 L EDS84AYCIB EN 4.0 - 11/2010
9.3.4 Read / Write
The "Read" PMS service reads parameters from the controller. The controller outputs the
requested parameter or an error message.
The "Write" PMS service writes to parameters of the controller. The controller outputs a
positive feedback or an error message.
The following error messages can occur:
9.3.5 Get-OD
The "Get-OD" PMS service reads out the object description for every parameter and data
type.
Error Class Error Code Additional
Code
[hex]
Description
6 3 0x00 No access authorisation
6 5 0x10 Impermissible job parameter
650x11Invalid subindex
6 5 0x12 Data length too big
6 5 0x13 Data length too small
6 6 0x00 Object is not a parameter
6 7 0x00 Object does not exist
6 8 0x00 Data types do not comply with each other
8 0 0x00 Job cannot be executed
8 0 0x20 Job currently cannot be executed
8 0 0x21 Cannot be executed because of local control
8 0 0x22 Cannot be executed because of device state
8 0 0x30 Quit value range / parameter can only be changed when the
controller is inhibited.
8 0 0x31 Value of the parameter is too high
8 0 0x32 Value of the parameter is too low
8 0 0x33 Subparameter outside the value range
8 0 0x34 Value of the subparameter is too high
8 0 0x35 Value of the subparameter is too low
8 0 0x36 Maximum value is lower than minimum value
8 0 0x41 Communication object cannot be displayed on process data
8 0 0x42 Length of the process data exceeded
8 0 0x43 General collision with other values