E84AYCIB communication manual (INTERBUS)
Technical data
Protective insulation
18 L EDS84AYCIB EN 4.0 - 11/2010
4.2 Protective insulation
Danger!
Dangerous electrical voltage
If Inverter Drives 8400 are used on a phase earthed mains with a rated mains
voltage 400 V, external measures need to be implemented in order to provide
reliable protection against accidental contact.
Possible consequences:
Death or serious injury
Protective measures:
If protection against accidental contact needs to be provided for the control
terminals of the controller and for the connections of the plugged-in device
modules, ...
a double isolating distance must exist.
the components to be connected must be provided with the second
isolating distance.
Note!
The protective insulation provided in Inverter Drives 8400 is realised in
accordance with EN 61800-5-1.