EDS84AYCIB EN 4.0 - 11/2010 L 37
E84AYCIB communication manual (INTERBUS)
Commissioning
Possible settings through DIP switch
6.2.3 Setting the baud rate
The baud rate can be set via switch 8 or code C13894
(for this, see Settings in the
»Engineer« ( 38)).
The current setting of the baud rate is displayed in C13863/
.
DIP switch Switch 8 Baud rate Max. cable length between adjacent nodes
OFF 500 kbps 400 m
ON 2 Mbps 150 m
12345678
ON
OFF