RG-MCMET 10
N2 Points
Point Description
1-11: Present Fault
This point indicates the type of fault on which the drive is currently tripped. This point returns
a value between 0 and 23 which corresponds to one of the following fault conditions:
Value Fault Value Fault
0 NO FAULT 12 POWER SAG
1 OUTPUT FAULT 13 CONTROL FAULT
2 RESERVED 14 LANGUAGE
3 HIGH DC BUS VOLTS 15 EXTERNAL FAULT
4 HIGH DRIVE TEMPERATURE 16 INTERNAL16
5 THERMAL OVERLOAD 17 POWER TRANSIENT
6 RESERVED 18 S/W ERROR #1
7 LOW DC BUS VOLTS 19 S/W ERROR #2
8 RESERVED 20 S/W ERROR #3
9 DC BRAKE ERROR 21 S/W ERROR #4
10 FOLLOWER LOSS 22 S/W ERROR #5
11 DB ERROR 23 GENERAL S/W ERROR
1-12: Recorded Fault 1
This point represents the most recent fault condition that has occurred according to the
same code scheme as for the present fault object. To clear the fault history, refer to Point
4-01 (Clear Fault History)
1-13: Recorded Fault 2
This point represents the 2nd most recent fault condition that has occurred.
1-14: Recorded Fault 3
This point represents the 3rd most recent fault condition that has occurred.
1-15: Recorded Fault 4
This point represents the 4th most recent fault condition that has occurred.
1-16: Recorded Fault 5
This point represents the 5th most recent fault condition that has occurred.
1-17: Recorded Fault 6
This point represents the 6th most recent fault condition that has occurred.
1-18: Recorded Fault 7
This point represents the 7th most recent fault condition that has occurred.
1-19: Recorded Fault 8
This point represents the 8th most recent fault condition that has occurred.