EDS94ARNExxxx EN 2.3 - 06/2014 L 251
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
CAN module (MXI2): Faulty emergency configuration [0x00ae0000]
CAN module (MXI2): Node guarding error 1 ... 32 [0x00af0000 ... 0x00a0001f]
CAN module (MXI2): Faulty NMT master configuration [0x00af0020]
CAN module (MXI2) RPDO1: Telegram not received or faulty [0x00b00000]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: CAN
emergency configuration is faulty.
Faulty download of an Engineer or PLC Designer
project
Invalid CAN emergency settings according to
DS301V402 in the Engineer or PLC Designer.
Repeat download
Correct CAN settings in the project and regenerate
project.
Response (Lenze setting printed in bold) Setting: C14612/1...32 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: Cyclic node
monitoring
CAN master has not received a response to a node
guarding telegram (remote transmission request
telegram) from node 1 ... 32 within the defined time.
Reactivate CAN node by mains switching, restart of
the regenerative power supply module,
(C00002
="11000") or CAN reset node.
Reparameterise the node guarding monitoring time
or switch off monitoring.
Reset locked error status if necessary.
Tip: Save the current parameter set before mains
switching and restarting the regenerative power supply
module (C00
002="11").
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: A
configuration error has occurred in the network
management of the CAN master.
Faulty download of an Engineer or PLC Designer
project.
Invalid CAN master settings according to DS301V402
and DS405 in the Engineer or PLC Designer.
Incorrect parameterisation of node guarding or
heartbeat.
Repeat download
Correct CAN settings in the project and regenerate
project.
Response (Lenze setting printed in bold) Setting: C14591/1 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: CAN-IN 1
error
Incorrect PDO telegram length.
Transmission error.
PDO time monitoring has responded.
Set the correct telegram length for the CAN master
(sender).
Eliminate disturbances in the environment (e.g. EMC).
Select a different monitoring time or switch off time
monitoring.