23 RG-MHMOD
Drive Control & Communication
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name Range of Adjustment
Modbus value (decimal value)
Factory Default
95 (5F) 44 TB10B OUT 00 - None
01 - 0 - 10 VDC
02 - 2 - 10 VDC
00 - None
96 (60) 45 @TB10B 10 - 200 (10 - 200%) 125 (125%)
98 (62) 47 TB13A 00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #1
04 - DEC FREQ
05 - REVERSE
00 - None
99 (63) 48 TB13B 00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #2
04 - INC FREQ
00 - None
100 (64) 49 TB13C 00 - None
01 - 0 - 10 VDC
02 - 4 - 20 mA
03 - PRESET #3
04 - HAND
05 - REVERSE
00 - None
101 (65) 50 TB13D 00 - EXT Fault
01 - EXT /Fault
02 - EXT Clear
00 - EXT Fault
103 (67)
104 (68)
105 (69)
52
53
54
TB14OUT
TB15OUT
RELAY
00 - None
01 - Run
02 - Fault
03 - INV Fault
04 - Fault Lockout
05 - @ Speed
06 - Above Preset #3
07 - Current Limit
08 - AUTO/HAND SRC
09 - FLWR PRESET
10 - MIN/MAX ALARM
11 - INV MIN/MAX ALM
12 - MIN ALARM
13 - INV MIN ALARM
14 - MAX ALARM
15 - INV MAX ALARM
16 - RUN REVERSE
00 - None
106 (6A) 55 TB5B LOSS 00 - Fault
01 - Preset #3
00 - Fault
108 (6C) 57 SERIAL 00 - Disable
01 - w/ Timer
02 - w/o Timer
00 - Disable
109 (6D) 58 ADDRESS 1 - 247 30
112 (70) 61 PASSWORD 0000 - 9999 0019
114 (72) 63 SOFTWARE (View Only) (N/A)