Parameter setting
6-18
BA2112EN
6.1.4 User defined control profile (C0009 = 12)
• Only useful with 93XX and 8200 vector (free configuration possible)
• When using a user-defined control profile, predefined control and status words are not
available.
• The user determines the link between input and output data.
• Function block assignment for 93XX (see chapter 6.1.1.4, ( 6-4) )
– Byte 3 and 4 form the input or output word W1
– Byte 5 and 6 form the input or output word W2
• Process data assignment for 8200 vector: see chapter 6.1.1.3, ( 6-3) .
For more information about the function blocks see the Manuals 93XX and 8200 vector.
Danger!
User-defined control is only allowed for 93XX and 8200 vector controllers!
If a speed has been selected via the corresponding process data word, the drive starts immediately
when the module is being attached.
Tip!
Please observe that bytes 7/8 of the control/status word shown in the diagram above cannot be
accessed via INTERBUS-Loop.
6.2 Process data monitoring
6.2.1 Process data monitoring time
If the process data transfer takes longer than t = 640 ms, the action set under parameter C0125
(Process data monitoring selection code) will be activated.
6.2.2 Process data monitoring selection code
Code Meaning
C0125 0: No action
1: No action
2: Unit control command “Inhibit voltage” (controller inhibit with latching in status “SWITCH ON INHIBIT”).
3: Unit control command “Quick stop” (QSP)withlatchinginstatus“SWITCH ON INHIBIT”
Danger!
• DRIVECOM control
– The latching function is active.
• Unit control
– The latching function must be implemented in the master!
Otherwise the machine starts automatically after the bus system has been activated if a
speed setpoint ≠ 0 has been set in the process data word.