Lenze 13466146 EDBSF01 v24 EN 17
Installation 3
NOTE
• Applicable national and local electrical codes take precedence over
recommendations in these tables.
• Use UL Class CC fast-acting, current limiting type fuses. Select fuses with low I
2
T values, rated at 200,000 AIC. Recommended fuses are Bussman KTK-R, JJN, and
JJS. Similar fuses with equivalent ratings by other manufacturers may also be
acceptable.
WARNING!
This product can cause a DC current in the protective conductor. Where a residual
current device (RCD) is used for protection in case of direct or indirect contact, only
an RCD of Type B is allowed on the supply side of this product. Otherwise, another
protective measure shall be applied, such as separation from the environment by
double or reinforced insulation, or isolation from the supply system by a transformer.
Observe the following when using RCDs:
1. Only install the RCD between the supply mains and drive controller.
2. The RCD can be activated by:
- capacitive leakage currents between the cable screens during operation
(especially with long, screened motor cables)
- connecting several drives to the mains at the same time
- additional RFI filters
3.2.3 Input Wire Size Requirements
WIRE SIZE REQUIREMENTS
208/240 Vac, 1 phase 208/240 Vac, 3 phase 400/480 Vac, 3 phase 480/590 Vac, 3 phase
MODEL AWG mm
2
MODEL AWG mm
2
MODEL AWG mm
2
MODEL AWG mm
2
SF203Y 14 2.5 SF203Y 14 2.5
SF205Y 14 2.5 SF205Y 14 2.5 SF405 14 2.5
SF210Y 12 4.0 SF210(Y) 14 2.5 SF410 14 2.5 SF510 14 2.5
SF215Y 12 4.0 SF215(Y) 14 2.5 SF415 14 2.5
SF220Y 10 6.0 SF220(Y) 12 4.0 SF420 14 2.5 SF520 14 2.5
SF230Y 10 6.0 SF230(Y) 10 6.0 SF430 14 2.5 SF530 14 2.5
SF250Y 8 6.0 SF250(Y) 10 10 SF450 14 2.5 SF550 14 2.5
SF275 10 10 SF475 12 4.0 SF575 14 2.5
SF2100 8 10 SF4100 10 6.0 SF5100 12 4.0
SF2150 6 16 SF4150 8 10 SF5150 10 6.0
SF2200 4 25 SF4200 8 10 SF5200 8 10
SF4250 6 16 SF5250 8 10
SF4300 6 16