13435743_EDBM301_v14.0 33
15 MC3000 CONTROL WIRING DIAGRAMS
15.1 MC3000 TERMINAL STRIP
Shown below is the terminal strip on the main control board, along with a brief description
of the function of each terminal. Wiring shown above the terminal strip indicates internal
wiring on the main control board.
FORM C
RELAY
1 2 5A 5B 6 10A 12A RXA TXB10B 2 13A 13B 13C 13D 14 15 2
16 17 18
STOP
CIRCUIT COMMON
0-10 VDC SPEED REFERENCE INPUT
10 VDC SUPPLY FOR SPEED POT
0-10 OR 2-10 VDC OUTPUT: FREQUENCY
0-10 OR 2-10 VDC OUTPUT: LOAD
CIRCUIT COMMON
START
TB-13A FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13C FUNCTION SELECT
TB-13D FUNCTION SELECT
OPEN-COLLECTOR OUTPUT
OPEN-COLLECTOR OUTPUT
RS-485 SERIAL
COMMUNICATIONS
CIRCUIT COMMON
4-20 mA SPEED REFERENCE INPUT
The TB-2 terminals are internally tied together
NOTE
The function of terminals TB-10A, TB-10B, TB-13A, TB-13B, TB-
13C, TB-13D, TB-14, TB-15, TB-16, and TB-18 are dependent on
the programming of certain parameters. In most cases, the name of
the parameter matches the number of the terminal, allowing quick
and easy programming of the terminals to suit the application. The
exception is TB-16 and TB-18, which are governed by Parameter
54 - RELAY.
A complete description of operating the drive in the REMOTE mode can be found in
Section 14.2. The following diagrams provide a quick reference to wire the drive for the
most common congurations.