Technical data
General data and application conditions
5
2111 INTERBUS fieldbus module
5.3
5.3.1
L
5.3-1
EDSIBS-1.0-06/2003
5.3 Technical data
5.3.1 General data and application conditions
Field Values
Order number EMF 2111IB
Communication media RS485
Network topology Ring
INTERBUS participant Slave
Communication profile PCP 1.5
Drive profile DRIVECOM profile 21
au
rate 5
t
s
Ambient temperature during operation:
during transport:
during storage
0 °C
-25
°C
-25
°C
to
to
to
55 °C
70 °C
60 °C
Permissible humidity Class 3K3 to EN 50178
(without condensation, average relative humidity 85%)
Degree of pollution VDE0110, part 2, pollution degree 2
Enclosure IP 20
Voltage supply (internal / external),
see
^ 5.4-5
External supply via separate power supply unit
(+24 V DC ±10 %, ma x. 150 mA)
5.3.2 Rated data
Insulation voltage between bus and ... Rated insulation voltage Type of insulation
• Earth reference / PE 50 V AC Mains isolation
• External supply (terminal 39/59) 0VAC No mains isolation
• Power stage
– 820X / 821X 270 V AC Basic insulation
– 822X / 8200 vector 270 V AC Double insulation
– 93XX 270 V AC Double insulation
• Control terminals
– 820X / 8200 vector
(with internal supply)
0VAC No mains isolation
– 8200 vector
(with external supply)
100 V AC Basic insulation
– 821X 50 V AC Mains isolation
– 822X 270 V AC Basic insulation
– 93XX 270 V AC Basic insulation
5.3.3 Protocol data
Field Values
Maximum number of participants 62
Process data words (PD) L-C1910 = 4: 2 words (32 bit)
L-C1910 = 6: 3 words (48 bit)
à Lenze setting
Parameter data words (PCP) 1(16bit)
Maximum number of data words The maximum number of data words (PD + PCP) is 4.
INTERBUS ID (module ID) 227
dec
=E3
hex
PCP 1 word
Maximum PDU length 64 byte
Supported PCP services Initiate, abort, status, identify, Get-0V-long, read, write