Lenze EMB934x Manual de usuario Pagina 108

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 206
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 107
Electrical installation
Regenerative power supply modules EMB9341 and EMB9342
Power connections
5
108
EDBMB9340 DE/EN/FR 12.0
5.3 Regenerative power supply modules EMB9341 and EMB9342
5.3.1 Power connections
Stop!
Please observe the following operating conditions:
ƒ Regenerative power supply modules must not be connected in parallel in
the DC bus.
ƒ The regenerative power supply module has no overload protection which
means:
– Please observe the permissible mains voltage and maximum currents
( 86). Higher voltages or currents destroy the regenerative power supply
module.
– For protecting the regenerative power supply module against overload
during the regenerative feedback we recommend the use of a brake
chopper. Please observe the circuit proposals ( 124).
ƒ Please observe national and local regulations!
Vista de pagina 107
1 2 ... 103 104 105 106 107 108 109 110 111 112 113 ... 205 206

Comentarios a estos manuales

Sin comentarios