2.12.17.14 Sd6 − motor temperature sensor monitoring
This monitoring function checks whether the motor temperature sensor supplies values within the
measuring range of −50 ... +250 °C.
If the values are out of this measuring range, monitoring is triggered.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x086 Sd6 Thermal sensor error MCTRL_bSensorFault
Lenze setting
Setting possible
The response is set under C0586:
Code LCD
Possible settings
IMPORTANT
Lenze Selection
C0594 MONIT SD6 Monitoring configuration: Motor
temperature sensor error
(X7 or X8)
Dependent on C0086
0 TRIP
2 Warning
3 Off
2.12.17.15 Sd7 − absolute value encoder monitoring
This monitoring function repeatedly reads in the absolute value of the encoder when the PLC is
switched on to find out if the same value is transmitted to the drive.
If a deviation > 5 % is detected at the motor shaft, the monitoring (TRIP) is actuated.
Error
Monitoring function System variable
Possible responses
No. Display TRIP Message Warning FAIL−QSP Off
x087 Sd7 Absolute value encoder error MCTRL_bEncoderFault_b
Lenze setting
Setting possible