2.9 DFOUT_IO_DigitalFrequency (node number 22)
9300 Servo PLC
System blocks
2−36
L
9300 Servo PLC EN 5.0
Configuration of the digital frequency output signal
The type of the digital frequency output signal is configured under C0540:
Code LCD
Possible settings
Info
Lenze Selection
C0540 Function 2 Digital frequency output: Function
X9 is inhibited if 0, 1, or 2 have
been selected.
DFOUT_nIn_v = 0 if 4 or 5 have
been selected.
The input signals are buffered
electrically.
0 DFOUT_nOut_v as %
1 DFOUT_nOut_v as rpm
2 Incremental encoder simulation + zero pulse
4 X9 is output on X10
5 X8 is output on X10
C0540 = 0 Output of an analog signal
Function The input signal DFOUT_nOut_v is interpreted as an analog signal [%] and is output as a frequency signal on the
digital frequency output X10.
Scaling 100 % (INT)16384 C0011 (n
max)
Transmission function
f[Hz] + DFOUT_nOut_v[%] @
StrichzahlausC0030
100
@
C0011(n
max
)
60
DFOUT_nIn_v + f[Hz] @
60
Strichzahl aus C0030
@
2
14
15000
Example
DFOUT_nOut_v = 50 %
C0030 = 3, this corresponds to a number of increments of 2048 increments/revolution
C0011 = 3000 rpm
f[Hz] + 50% @
2048
100
@
3000
60
+ 51200Hz
C0540 = 1 Output of a speed signal
Function The input signal DFOUT_nOut_v is interpreted as a speed signal [rpm] and is output as a frequency signal on the
digital frequency output X10.
Scaling 15000 rpm (INT)16384
Transmission function
f[Hz] + DFOUT_nOut_v[rpm] @
Strichzahl aus C0030
60
Example
DFOUT_nOut_v = 3000 rpm
C0030 = 3, this corresponds to a number of increments of 2048 increments/revolution
f[Hz] + 3000rpm @
2048
60
+ 102400Hz
C0540 = 2 Encoder simulation of the resolver with zero track in resolver position
Function The function is used if a resolver is connected to X7.
The encoder constant for the output X10 is set under C0030.
The output of the zero pulse referring to the rotor depends on how the resolver is attached to the motor.
The zero pulse can be shifted by +360 ° under C0545 (65536 inc = 360 °).
C0540 = 4 Direct output of X9
Function Use of X9 as a digital frequency input.
The input signal at X9 is electrically amplified and is directly output to X10.
The signals depend on the assignment of input X9.
C0030 and C0545 have no function.
The zero track is only output if it is also connected to X9.
C0540 = 5 Direct output of X8
Function Use of X8 as an input for incremental encoders or sin/cos encoders.
The input signal at X8 is electrically amplified and is directly output to X10.
The signals depend on the assignment of input X8.
C0030 and C0545 have no function.
The zero track is only output if it is also connected to X8.