Lenze E84DGFCG Manual de usuario Pagina 114

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 149
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 113
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013 114
Implemented CIP™ objects
General CIP objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Instance attributes for output data of the scanner
Assembly output objects (scanner to adapter) are assumed to have a 4-byte header (32-bit "run/idle
header"). When mapping the assemblies, this header will automatically be added to the data
stream by most Allen-Bradley PLC/SLC equipment.
If your PLC does not support this header (like the Rockwell PLCs do), add a preceding 32-bit header
to the output image.
You can then define the bit 0 of this header in the process image of your PLC:
State ’0’: idle mode
State ’1’: run mode
For the operation with Rockwell PLCs, adaptations are not required.
The Lenze Class (104 / 0x68)
( 142) provides the image of the output data of the scanner.
Attribute
ID
Service Name Data type Value
3 Get / Set Data ARRAY of
SINT / INT /
DINT
Max. 16 bytes from the scanner to the
adapter:
• 20 (0x14): Basic Speed Control Output
• 21 (0x15): Extended Speed Control
Output
• 22 (0x16): Speed and Torque Control
Output
• 23 (0x17): Extended Speed and Torque
Control Output
• 110 (0x6E): Custom Output
Instance attribute "Data" (attribute 3)
( 116)
4 Get Size UINT Number of bytes in attribute 3 (Data)
Vista de pagina 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 148 149

Comentarios a estos manuales

Sin comentarios