Lenze · I/O system 1000 · commissioning guidelines for the PLC Designer · DMS 1.2 EN · 11/2012 · TD05 9
2 System and product description
2.3 Device architecture
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2.3 Device architecture
Device architecture of the I/O system 1000
Bus coupler module
•CANopen: EPM-S110
•PROFIBUS: EPM-S120
•EtherCAT: EPM-S130
I/O compound modules, max. 64
n Connection to the bus system (CANopen/EtherCAT)
• CANopen, PROFIBUS: via a 9-pole Sub-D plug (see illustration)
• EtherCAT: RJ45, double
o Internal backplane bus for communication between the bus coupler module and the I/O compound modules
• Side-by-side mounting of the module feet of the I/O compound modules provides for the electrical
connection to the bus coupler module.
p Supply voltage DC 24 V, max. 10 A for consumers at output modules
• Side-by-side mounting of the module feet of the I/O compound modules provides for the electrical
connection to the bus coupler module.
q Supply voltage DC 24 V for the electronics
• Side-by-side mounting of the module feet of the I/O compound modules provides for the electrical
connection to the bus coupler module.
0